TSSHC-3DPAS-2/4/7GFCI or TSSHC-3DPFS-2/4/7GFCI
INSTRUCTIONS
The
thermostat is an electronic on/off thermostat for control of temperature by
means of an NTC sensor either placed externally or internally in the thermostat.
The thermostat has integrated a Ground Fault Circuit Interrupter (GFCI, Class
A). The thermostat and the GFCI is a dual model suitable for 120/240 V 50/60 Hz
supply. The thermostat is for flush
mounting in a wall socket.
Product
program
Clock-Thermostats
with built-in GFCI
TSSHC-3DPFS-2/4/7GFCI ----
Incl. floor sensor 3 m
TSSHC-3DPAS-2/4/7GFCI
----With built-in room sensor
Mounting
of floor sensor (fig. 3)
The
floor sensor is used for temperature regulation in floor surfaces. For easy
replacement the sensor can be mounted in a tube which is placed between 2
heating cables. The tube is ended
towards the floor surface and sealed. If
required, the sensor cable can be extended up to about 100 m with a standard
installation cable. 2 leads in a multi lead cable, which is used as supply cable
for the heating cable, must not be used.
Mounting
of thermostat with built-in sensor
(fig.
4)
The
room sensor is used for comfort temperature regulation in rooms. The thermostat
is mounted on the wall with free air circulation about 4 ft or 1.2 m above the floor,
next to the light switch.
Draught, direct sunlight, or any other direct heating outlet
Mounting
of thermostat
Installation
TURN
OFF THE POWER TO THE HEATING SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL
SHOCK. KEEP AIR VENTS OF THE THERMOSTAT CLEAN AND OBSTRUCTION FREE.
This
thermostat is an electrical product and must be installed in conformity with the
National and/or Local Electrical Code. The installation must be performed by
qualified personnel where required by law. The thermostat is equipped with a
ground fault circuit interrupter (GFCI, Class A), which require that the line
and load is isolated from each other for correct operation. The resistive load
must not exceed16A (1920W at 120Vac /3840W at 240Vac). During a ground fault,
the two lines will be cutoff.
Line Power
Delivers
power from the service panel (breaker panel or fuse box) to the thermostat.
This cable shall only be connected to the thermostat’s line terminals
marked L1 and L2.
Load to Panel or Ceiling
Delivers
power from the thermostat to the heating cable.
This
cable shall only be connected to the thermostat’s load terminals marked load,
16A.
1.
Use a screwdriver to open the lock (fig. 1), and remove the frame
2.
Connect cables according to the diagram (fig. 2)
3.
The thermostat is mounted in the wall socket. The frame are remounted.
Temperature
sensor
The floor sensor is connected to the screw less terminals marked sensor. Push with a screwdriver on the terminal spring and mount the wires.
click on photo for a larger view
Operation
With
integrated clock:
The
first time the thermostat is connected, time and day must be set:
Setting
of time (the clock flashes during setting)
Setting
of day (day flashes during setting)
Without
integrated clock:
Actual
temperature setting is shown and the thermostat is ready for use.
Checking
GFCI
It
is important that the GFCI has been checked for correct installation and
function.
To
check the GFCI:
Testing
can only be performed if the thermostat has a heating demand.
Adjust the set point until the heating symbol (SSS) appears, use the (
),
to increase the heating demand. Wait 10 sec to let the thermostat work according
to the new set point.
Press
the button "TEST"
The
test is conclusive if the red light on the thermostat lightens, and the display
signs disappear. If this does not occur, check the installation.
Press
on RESET button to reset the GFCI.
The
red light should disappear and the display will return to normal appearance.
Push ok accept button (
) to cancel the previously set temperature If the test
fails, check your heating cable and the thermostat.
The GFCI test should be carried out monthly.
If the GFCI trips in normal operation, without pressing the TEST button,
there could be a
ground
fault! To check whether it is a ground fault or a nuisance tripping, press
RESET. If this cause the red light to shot off and not comes on again, it was a
nuisance tripping and the system is functioning. If this cannot be done there is
a ground fault! Check your heating
cable, the sensor cable and the thermostat. Exchange the defective part.
Programming
See
user’s manual.
Fault
location
If
the sensor is disconnected or short-circuited, the heating system is cut out.
The sensor can be checked according to the resistance table fig. 5.
Error
codes
E0:
Internal error. The thermostat must be replaced.
E1:
Built-in sensor short-circuited or disconnected. The thermostat must be replaced
E2:
External sensor short-circuited or disconnected.
UL
LISTED
According
to the following standards,
GFCI:
UL 943:1993
Thermostat:
UL 8730-2-9:1998; UL 60730-1A:2002
UL
file number: E157297.
Classification
The
product is a class II device (enhanced insulation) and the product must be
connected to the following leads:
Phase
(L, L1) 240 V ±15%, 50/60 Hz or 120 V ±15%, 50/60 Hz
Neutral
(N, L2)
Load
max. 16A
The
terminals are suitable for field wiring of 12 AWG to 22 AWG conductors
Technical
Data
Supply
. . . . . . . . . . . . . .120/240 Vac 50/60 Hz
Load
. . . . . . . .16A maximum (resistive load)
Power
. . . . . . . . . . . . . . . .1.920 W at 120 Vac
. . . . . . . . . . . . . . . .3.840 W at 240 Vac
GFCI
. . . . . . . . . . . .Class A (5 mA trip level)
Temperature
range .+5 to +40°C, +40 to +104°F
Amb.
Temperature range Thermostat . . . . . . . .0 to +40°C, +32 to +104°F
GFCI
. . . . . . . . .-35 to +65°C, -31 to +149°F
