Quick System Sizing...

Design Guidelines

1)    Determine panel size by selecting a balanced combination of Enerjoy Peopleheaters to cover 10% of the ceiling surface.

2)    Design symmetrical heatmodule placement in the same way you locate lights to illuminate a room, recognizing areas of high heat loss and special comfort areas.

3)    Take full advantage of the broad dispersion of radiant energy emanating at a 80° angle from the heatmodule surface. It is all right to over size[1] by using identical heatmodules to attain symmetry even though the sizing chart calls for unequal or smaller units.

Rules of Thumb:1) Select a geometrically pleasing design, while allowing a 2' to 4' setoff[2] from exterior walls and figuring approximately two times the setoff distance between Peopleheaters. 2) Use the following general specifications to determine watts per square foot (W/SF) of room area: Bath areas: 7 W/SF; Living room or corner offices: 6 W/SF; Dens, offices, dining rooms or corner bedrooms: 5W/SF; Kitchens or middle bedrooms: 4 W/SF.  Above 7,000 degree days add 1 W/SF.

[1]The sizing increase or decrease determines cycle frequency- how quick the thermostat setpoint is satisfied.

[2]There is no set off restriction.   Unnecessary heat loss is minimized

Enerjoy Peopleheater Selection

Room (typical) Size (feet) Area (SQ.FT.) New Construction
(8' ceilings)
Thermostat

Closet/powder

4 x 5 20-30 22RP or 22RPFL 1
Standard bath 5 x 7 35-50 23RP, 24RP or 23RPFL 1
Large bath 8 x 10 75-100 25RP or 25RPFL 1
Den/office 8 x 10 75-100 24RP or 25RP 1
Corner bed 12 x 12 130-160 28RP or 2-24RP 1
Middle bed 12 x 12 130-160 26RP 1
Lg. Corner bed 13 x 15 170-210 2-25RP or 2-26RP 1
Lg. Middle bed 13 x 15 170-210 28RP or 2-24RP 1
Standard Kit. 9 x 12 150-180 24RP 1
Lg. Kitchen 11 x 15 150-18 26RP or 2-23RP 1
Stand. Dining 8 x 12 90-120 25RP or 2-23RP 1
Lg. Dining 12 x 14 150-190 28RP or 2-24RP 1
Stand. Living 12 x 15 160-200 2-26RP 1
Lg. Living 14 x 20 260-300 3-28RP 1
Wiring note: Existing 20 amp 120 volt lighting circuits may serve Enerjoy I Heatmodules.
Insulation note:  Insulate floor above basement or crawlspace.

Additional Guidelines:

Supplemental heating:  basements and super-insulated houses- Use 1-24RP for each 100 sq. ft. of space--approx. 3-4 W/SF.

Cathedral ceilings or 10' ceilings:
       For 12' peak (avg. 10') increase heat panel area by 25%.  Ex.- Use 28RP instead of 26RP.
       For 16' peak (avg. 12') increase heat panel size by 50%. 

Split Levelbuildings- Add one watt per square foot.

Fireplaces, sliders or skylights- Add one watt per square foot.

 

TYPICAL ENERJOY® SIZING CHARTS

MODEL ENERGY CODE SPECIFICATIONS

OPERATIVE TEMPERATURE 70°F

ROOM DIMENSIONS 15 x 15 x 8

MIDDLE ROOM – 1 OUTSIDE WALL
ENERJOY SELECTION:
  • 1 Window, 5°F – 700w
        1 - 27RP 700w heatmodule
  • 2 Windows, -15°F – 1100w
        2 - 26RP 600w heatmodules
  • 1 Slider, -15°F – 1250w
        2 - 26RP 600w heatmodules
  • 1 Slider, 5°F – 950w
        1 - 45RP 1000w heatmodule
CORNER ROOM – 2 OUTSIDE WALLS
ENERJOY SELECTION:
  • 2 Window, 5°F – 800 Watts
        2 - 24RP 400w heatmodules
  • 2 Windows, -15°F – 1100w
        2 - 26RP 600w heatmodules
  • 4 Windows, 5°F – 1000w
        2 - 25RP 500w heatmodules
  • 4 Windows, -15°F – 1250w
        2 - 26RP 600w heatmodules
  • 2 Windows & 1 Slider   
        5°F - 1000w , 2 – 25RP
        -15°F – 1300w, 2 – 27RP

BUILDING SPECS: Wall: R-19; Floor: R-19; Ceiling: R-38; Glass: R-2 (above graphs assume window size of 3’x4’ & Sliding glass doors of 6’x6’8”); Air changes per hour: 0.25.
CHART USAGE: 1) Compute window percentage of outside wall; 2) Find intersection with Design Temperature; 3) Select ENERJOY Module(s) to meet wattage.
PLACEMENT: Parallel to and centered with 2’ offset from outside wall; second panel, if required, will be aligned with the first and separated approximately 4’ to 6’, or the distance necessary to achieve geometric layout balance